For the complete documentation index, see llms.txt. This page is also available as Markdown.

Titan Mini (30kW)

In addition to the General Requirements mentioned here, the device specific requirements for DeCharge Titan Mini (30kW) device are as follows:

Mounting and Foundation

  • Concrete base prepared as per DeCharge installation blueprint

  • Safety clearance of at least 0.5 meters on all sides

  • Anchor bolts installed and visible

  • Canopy or shed installed for protection

Power Input Requirements

Voltage
Transformer
Cable Size
Breaker Size

415V

50 KVA

35 sq.mm aluminium or 25 sq.mm copper

72A

  • Breaker panel must be within an accessible range

  • Neutral wire of 0.5 core must be connected using proper lugs

  • Neutral-to-earth voltage must be below 2V

Earthing

  • Two earthing pits required

  • Cabling: 25 x 3 mm tinned copper bus bar or 25 sq.mm single-core copper wire

  • Lugs: Ring-type aluminium or copper lugs for grounding points

Internet Connectivity

  • LAN: Cat6 cabling with proper termination and surge protection

  • 4G/5G SIM: Valid SIM with strong signals

  • Wi-Fi: High-speed router, no competing devices, good coverage

Safety Infrastructure

  • Safety bollards installed

  • LED lighting in place

  • Fire suppression systems if required by local code

  • Security arrangements if in a commercial or public location

Documentation Required

  • Confirmation of grid connection or power availability

  • Approved CMS form with device mapping

  • Signature of host or location owner

  • Photographs of breaker, cables, and mounting area

Please fill out the interest-cum-pre-requisite form if you're interested in installing a 30kW Titan Mini DC Charger at your location:

Alternatively, you can make a copy of this below document, fill it out, and send it to our email: [email protected]:

Last updated