Titan Mini (30kW)

In addition to the General Requirements mentioned here, the device specific requirements for DeCharge Titan Mini (30kW) device are as follows:

Mounting and Foundation

  • Concrete base prepared as per DeCharge installation blueprint

  • Safety clearance of at least 0.5 meters on all sides

  • Anchor bolts installed and visible

  • Canopy or shed installed for protection

Power Input Requirements

Voltage
Transformer
Cable Size
Breaker Size

415V

50 KVA

35 sq.mm aluminium or 25 sq.mm copper

72A

  • Breaker panel must be within an accessible range

  • Neutral wire of 0.5 core must be connected using proper lugs

  • Neutral-to-earth voltage must be below 2V

Earthing

  • Two earthing pits required

  • Cabling: 25 x 3 mm tinned copper bus bar or 25 sq.mm single-core copper wire

  • Lugs: Ring-type aluminium or copper lugs for grounding points

Internet Connectivity

  • LAN: Cat6 cabling with proper termination and surge protection

  • 4G/5G SIM: Valid SIM with strong signals

  • Wi-Fi: High-speed router, no competing devices, good coverage

Safety Infrastructure

  • Safety bollards installed

  • LED lighting in place

  • Fire suppression systems if required by local code

  • Security arrangements if in a commercial or public location

Documentation Required

  • Confirmation of grid connection or power availability

  • Approved CMS form with device mapping

  • Signature of host or location owner

  • Photographs of breaker, cables, and mounting area

Please fill out the interest-cum-pre-requisite form if you're interested in installing a 30kW Titan Mini DC Charger at your location:

Alternatively, you can make a copy of this below document, fill it out, and send it to our email: [email protected]:

Last updated

Was this helpful?